The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
46
indicate cases, when this difference is
exceeded.
026Bh F77
0..255
Allowable difference between set value and
read out value for channel 8. Alarm will
indicate cases, when this difference is
exceeded.
026Ch F78
Free
026Dh F79
Free
026Eh F80
0..1
PT-100 measurement range
0 – range up to 400°C
1 – range up to 600°C
026Fh F81
0..1
Recording base 0 – seconds
1 – minutes
0270h F82
0..1
Digital filter for the AC converter on / off 0 – filter off
1 – filter on
0271h F83
0..1
Transmission speed 0 – 9600 bps
1 – 19200 bps
(THE ONLY TRANSMISSION SPEED
AVAILABLE FOR MODBUS RTU
PROTOCOL IS 9600, SET PROPER
VALUE
)
0272h F84
0/1
Printing base 0 – seconds
1 – minutes
0273h F85
0..1
Clock / time-meter
“0”- displays real-time clock
“1” – displays impulse counter on
the 0/1 24V DC input
0274h F86
0..1
Relay status – REL 9 “0” – relay as an alarm signalling
device
“1” – relay as the 3-rd state in a 3-
state algorithm for channel 1
0275h F87
0..1
Relay status – REL 10 “0” – relay off
“1” – relay as the 3-rd state in a 3-
state algorithm for channel 2
0276h F88
0..1
Relay status – REL 11 “0” – relay as an alarm signalling
device
“1” – relay as the 3-rd state in a 3-
state algorithm for channel 3
0277h F89
0..1
Relay status – REL 12 “0” – relay as an alarm signalling
device
“1” – relay as the 3-rd state in a 3-
state algorithm for channel 4
0278h F 90
0..3
Measurement processing type for channel 1 “0” – actual value at the moment of
recording
“1” – average value in sampling
period (measurement every two
seconds)
“2” – maximum value
“3” – minimum value