The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
34
MODBUS RTU
The DLM-080 digital recorder communicates with master systems through two-wire serial
link (RS-485) using two transmission protocols: MIKSTER-BUS (protocol used in-house
by MIKSTER) and MODBUS RTU.
MODBUS RTU FRAME
T1 T2 T3 Device
Address
Function Data Control
Total
CRC-16
T1 T2 T3
8 bit 8 bit n x 8 bit 16 bit
Functions available from the DLM-080 recorder using the MODBUS protocol:
Function
number
Definition
0
Reserved
1
Reserved
2
Reserved
3
Reserved
4 Readout of DLM-080 records
5..64
Reserved
65 RTC clock setting in the DLM-080
66 Setting of highlighted measure using the DLM-080 keyboard
67 Transmission of SETUP settings to the DLM-080
68 Clearing of recording buffer
69..255
Reserved